Online Machine Diagnosis System

MK-720 Corona Discharge Checker

MK-720 enables finding of insulation deterioration on insulators, disconnectors, and circuit breakers, at hot-line condition!

POINT 1
Non-contact checking at hot-line condition is enabled by ultrasonic discharge sound detection.
POINT 2
MK-720 distinguishes discharge from other noises by frequency analysis.
POINT 3
Precise detection in ±8 area.
POINT 4
MK-720 records measurement data. And the data is easily transferable to PC via USB cable.
POINT 5
MK-720 generates audible sound from Corona discharge and transmits through an earphone.

Brochure Download

Principle

Corona discharge induced by insulation deterioration of AC power facility generates ultrasonic wave on wide band.
Twice-frequency is clearly observed by frequency analysis of enveloped ultrasound because this ultrasonic wave changes its intensity synchronizing with phase of electric power.
MK-720 can detect discharge without influence of sounds occurred from other source by detecting strength of twice-frequency.



PAGE TOP

Specifications

Power supply 4 dry AA battery (For continuous 8 hours operation)
Size 174mm (W) × 272mm (H) × 98mm (D)
Mass Approx. 400grams (excluding batteries)
Standard configuration 1 Main unit, 1 USB cable, 4 dry AA batteries, 1 earphone, 1 communication software (CD-Rom, MK-9804), 1 strap, 1 Instruction manual
Option Carrying case (MK-9703), Carrying bag (MK-9702), Reference ocsilator (MP-161)

Machine diagnosis instrument, Vibrometer and Isolation deterioration checker

  • JFE Advantech
  • Service and Support Phone:+81-3-5825-5577 Fax:+81-3-5825-5591
  • Request for documents